Reduced earth Armored, XLPE Insulated, PVC sheathed Power Cable (NC2XRY 3 X 35 RS + 10 RS)

Description

Description

Standards

  • Product
    IEC 60228 Class 2 ; IEC 60502-1

Scope

This specification covers PVC insulated, multicore armoured cables, rated at 0.6/1 KV to international standard IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.

Construction

2.1 Conductor
Plain, annealed copper conductors, circular stranded conforming to the applicable requirements of IEC 60228.

2.2 Insulation
XLPE insulation conforming to the applicable requirements of IEC 60502-1.

2.3 Assembly
Insulated conductors are laid up, filled where necessary with non-hygroscopic material and covered with an extruded thickness of thermoplastic material.

2.4 Amour
Galvanized round wires, completely covering the assembly of cores; complying to the applicable requirements of IEC 60502-1.

2.5 Sheath
PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
Galvanised round steel wires
Conductor flexibility
Class 2 acc. to IEC 60228
Conductor material
Annealed copper
Conductor shape
Circular compacted
Insulation
Cross-linked polyethylene
Material of bedding
Extruded compound
Material of filler / inner sheath
Filler if necessary
With smaller neutral conductor
Yes

Dimensional characteristics

Dimensional characteristics

Average insulation thickness
0.9 mm
Diameter over insulation
8.7 mm
External lay direction
Z
Insulation thickness of neutral conductor
0.70 mm
Maximum outer diameter
31.9 mm
Neutral Conductor Diameter
3.8 mm
Nominal Diameter under armour
23.0 mm
Nominal outer diameter
29.8 mm
Nominal outer sheath thickness
1.8 mm
Nominal weight
2246.6 g/m
Number of cores
4
Phase Conductor Diameter
6.9 mm

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.524 Ohm/km
Permissible current rating buried/duct 20°C
101 A
Permissible current rating in open air
88 A
Rated Voltage Uo/U (Um)
0,6/1 kV
Resistance of neutral conductor at 20ºC
1.83 Ohm/km

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Bending factor when installed
10 (xD)
Max. conductor temperature in service
90 °C
Metric marking
METRIC MARKING
Operating temperature, range
-25 ... 55 °C
U.V resistance
Yes

Resources

Resources

Selling & delivery Information

Made in different lengths based on customer's requirement.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close