Single core AWA Armored, XLPE insulated, PVC sheathed
Single core AWA Armored, XLPE insulated, PVC sheathed
0.6 / 1 KV POWER CABLES Conforming to IEC 60502-1
Read moreEXW 1*10
Nexans ref. EXW 000408
- Conductor cross-section: 10 mm²
- Nominal insulation thickness: 0.7 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal overall diameter: 13.0 mm
- Approximate weight: 261 kg/km
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 80 A
- Permissible current rating when buried: 91 A
EXW 1*1000
Nexans ref. EXW 001713
- Conductor cross-section: 1000 mm²
- Nominal insulation thickness: 2.8 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 2.7 mm
- Nominal overall diameter: 59.0 mm
- Approximate weight: 10980 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0176 Ohm/km
- Permissible current rating in open air: 1250 A
- Permissible current rating when buried: 1115 A
EXW 1*120
Nexans ref. EXW 000631
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 1.2 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.7 mm
- Nominal overall diameter: 23.0 mm
- Approximate weight: 1475 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 379 A
- Permissible current rating when buried: 363 A
EXW 1*150
Nexans ref. EXW 000641
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 1.4 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.7 mm
- Nominal overall diameter: 25.0 mm
- Approximate weight: 1767 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 435 A
- Permissible current rating when buried: 405 A
EXW 1*16
Nexans ref. EXW 000413
- Conductor cross-section: 16 mm²
- Nominal insulation thickness: 0.7 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal overall diameter: 13.5 mm
- Approximate weight: 332 kg/km
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 107 A
- Permissible current rating when buried: 118 A
EXW 1*185
Nexans ref. EXW 000651
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 1.6 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal overall diameter: 27.0 mm
- Approximate weight: 2160 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 496 A
- Permissible current rating when buried: 457 A
EXW 1*2.5
Nexans ref. EXW 001303
- Conductor cross-section: 2.5 mm²
- Nominal insulation thickness: 0.7 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal overall diameter: 11.0 mm
- Approximate weight: 155 kg/km
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 33 A
- Permissible current rating when buried: - A
EXW 1*240
Nexans ref. EXW 000661
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 1.6 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal overall diameter: 30.0 mm
- Approximate weight: 2715 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 584 A
- Permissible current rating when buried: 529 A
EXW 1*25
Nexans ref. EXW 000414
- Conductor cross-section: 25 mm²
- Nominal insulation thickness: 0.9 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal overall diameter: 15.0 mm
- Approximate weight: 450 kg/km
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 142 A
- Permissible current rating when buried: 148 A
EXW 1*300
Nexans ref. EXW 000671
- Conductor cross-section: 300 mm²
- Nominal insulation thickness: 1.8 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 2.0 mm
- Nominal overall diameter: 32.0 mm
- Approximate weight: 3322 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 665 A
- Permissible current rating when buried: 600 A
EXW 1*35
Nexans ref. EXW 000419
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 0.9 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal overall diameter: 16.0 mm
- Approximate weight: 554 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 175 A
- Permissible current rating when buried: 179 A
EXW 1*4
Nexans ref. EXW 001002
- Conductor cross-section: 4 mm²
- Nominal insulation thickness: 0.7 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal overall diameter: 11.5 mm
- Approximate weight: 179 kg/km
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 45 A
- Permissible current rating when buried: - A
EXW 1*400
Nexans ref. EXW 000678
- Conductor cross-section: 400 mm²
- Nominal insulation thickness: 2.0 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal overall diameter: 37.0 mm
- Approximate weight: 4266 kg/km
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 779 A
- Permissible current rating when buried: 690 A
EXW 1*50
Nexans ref. EXW 000421
- Conductor cross-section: 50 mm²
- Nominal insulation thickness: 1.0 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.5 mm
- Nominal overall diameter: 18.0 mm
- Approximate weight: 710 kg/km
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 212 A
- Permissible current rating when buried: 214 A
EXW 1*500
Nexans ref. EXW 000684
- Conductor cross-section: 500 mm²
- Nominal insulation thickness: 2.2 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal overall diameter: 41.0 mm
- Approximate weight: 5355 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0366 Ohm/km
- Permissible current rating in open air: 870 A
- Permissible current rating when buried: 780 A
EXW 1*6
Nexans ref. EXW 001006
- Conductor cross-section: 6 mm²
- Nominal insulation thickness: 0.7 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.4 mm
- Nominal overall diameter: 12.0 mm
- Approximate weight: 209 kg/km
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 58 A
- Permissible current rating when buried: 68 A
EXW 1*630
Nexans ref. EXW 000691
- Conductor cross-section: 630 mm²
- Nominal insulation thickness: 2.4 mm
- Nominal armour wire diameter: 2 mm
- Nominal outer sheath thickness: 2.3 mm
- Nominal overall diameter: 45.0 mm
- Approximate weight: 6825 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0283 Ohm/km
- Permissible current rating in open air: 995 A
- Permissible current rating when buried: 880 A
EXW 1*70
Nexans ref. EXW 000611
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 1.1 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.6 mm
- Nominal overall diameter: 19.5 mm
- Approximate weight: 933 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 270 A
- Permissible current rating when buried: 264 A
EXW 1*800
Nexans ref. EXW 000703
- Conductor cross-section: 800 mm²
- Nominal insulation thickness: 2.6 mm
- Nominal armour wire diameter: 2.5 mm
- Nominal outer sheath thickness: 2.5 mm
- Nominal overall diameter: 53.0 mm
- Approximate weight: 8981 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0221 Ohm/km
- Permissible current rating in open air: 1145 A
- Permissible current rating when buried: 990 A
EXW 1*95
Nexans ref. EXW 000615
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 1.1 mm
- Nominal armour wire diameter: 1.7 mm
- Nominal outer sheath thickness: 1.6 mm
- Nominal overall diameter: 21.0 mm
- Approximate weight: 1200 kg/km
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 327 A
- Permissible current rating when buried: 317 A
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-1
-
TestIEC 60332-1-2
Scope
This specification covers PVC, circular, single core armoured cables, rated at 0.6/1 KV according to IEC 60502-1 for use indoors, outdoors, in cable ducts and for direct burial underground, where severe mechanical stresses are present.
Construction
2.1 Conductor
Plain, annealed electrolytic copper conductors, circular stranded, conforming to the applicable requirements of IEC 60228.
2.2 Insulation
XLPE insulation, conforming to the applicable requirements of IEC 60502-1.
2.3 Armour
Aluminum wires armor, complying to the applicable requirements of IEC 60502-1.
2.5 Sheath
PVC based thermoplastic material, conforming to the applicable requirements of IEC 60502-1.
2.6 TESTS
Conforming to the applicable requirements of IEC 60502-1 either on Raw materials or on finished products.
TEST AT WORKS according to IEC 60502-1 armored
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2
- Voltage test acc. to IEC 60502-1 parag. 15.1 & 15.3
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.
Sample Tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation: according to IEC 60502-1 Parag. 16.5.2
Armour: according to IEC 60502-1 Parag. 16.7
Oversheath: according to IEC 60502-1 Parag. 16.5.3
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-1.
These tests will be carried out on one length of the order .
Tests certificates will be provided by Liban Cables
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania